Henderson-Nina Water System, Inc.

 Cross Connection Policy

 LDHH-OPH-ENGINEERING SERVICES SECTION

 MODEL ORDINANCE ON CROSS CONNECTION CONTROL

Sec. 13-4. Cross-Connection Control Device or Method Required.

 Each existing or new structure is required to implement and maintain an
adequate cross-connection control device or method for backflow prevention as
mandated under state law and state regulations.

Sec. 13-5. Definitions.

 The following definitions shall apply only to this Division. For those terms
not defined in this Division, the definitions contained in the Louisiana State
Plumbing Code 2000 edition (LSPC, 2000 Edition), and as amended, shall apply.

1. “Administrative authority” means the Henderson-Nina Water System, or any
agent, employee, officer, department, or board of the City designated to enforce this
ordinance.

2. “Approved” means accepted or acceptable under an applicable specification or
standard stated or cited in the code, or accepted as suitable for the proposed use under
procedures and authority of the administrative authority.

3. “Approved backflow prevention assembly for containment” means an air gap
meeting ASME Standard A 112.1.2 - 1991 (R 1998) “Air Gaps in Plumbing Systems” or
a backflow prevention assembly which is listed by the University of Southern California-
Foundation for Cross Connection Control and Hydraulic Research (USC-FCCCHR) as
having met the requirements of ANSI/AWWA Standard C510-97 or ASSE Standard
1015-1993, “Double Check Valve Backflow-Prevention Assemblies”, or ANSI/AWWA
Standard C511-97 or ASSE Standard 1013-1993, “Reduced-Pressure Principle Backflow
Assemblies” for containment. The listing shall include the limitations of use based on the
degree of hazard. The backflow prevention assembly must also be listed by the ASSE in
Table 606 of the LSPC, 2000 Edition or other testing agency approved by the
administrative authority. This term shall additionally include those backflow prevention
assemblies meeting ANSI/ASSE Standard 1047-1995, “Backflow Preventer, Reduced
Pressure Detector Assembly”, or ANSI/ASSE Standard 1048-1995, “Backflow Preventer,
Double Check Detector Assembly”. (These detector assembly devices are often times
used on fire protection/fire sprinkler systems to detect and monitor unauthorized water
usage.)
4. “Approved backflow prevention assembly for containment in fire protection
system” means a backflow prevention assembly listed in Table 606 of the LSPC, 2000 Edition to
be used in a fire protection system which also meets the requirements of Factory Mutual
Research Corporation (FM) and Underwriters Laboratory (UL) and the requirement of the
standard Codes adopted by the Henderson-Nina Water System. Devices sized smaller than 2½
inches, which have not been listed by Underwriters Laboratory (UL) and tested by Factory
Mutual Research Corporation (FM), may be allowed if approved by the State Fire Marshal, and
such device is listed in Table 606 of the LSPC, 2000 Edition. Any such device under this
definition shall minimally meet the definition of an “approved backflow prevention assembly for
containment”. In addition, the particular type of device to be used for a particular
application/degree of hazard shall be selected and installed in accord with the requirements of
Table D104 of the LSPC, 2000 Edition.

5. “Approved testing agency” means an organization primarily established for purposes
of testing to approved standards and approved by the administrative authority (e.g., American
Society of Mechanical Engineers (ASME), American Society of Sanitary Engineers (ASSE),
American Water Works Association (AWWA), American National Standards Institute (ANSI),
Factory Mutual Research Corporation (FM), Underwriters Laboratory (UL), University of
Southern California-Foundation for Cross Connection Control and Hydraulic Research (USC-
FCCCHR), etc.).

6. “Auxiliary water supply” means any water supply on or available to the premises other
than the water purveyor's approved public water supply such as, but not limited to, a private well,
pond or river.

7. “Backflow” means the flow of water or other liquids, mixtures, or substance into the
distribution pipes of a potable supply of water from any sources other than its intended source.

8. “Backflow connection” means any arrangement whereby backflow can occur.

9. “Back-pressure backflow” means backflow due to an increased pressure above the
supply pressure. This may be due to pumps, boilers, gravity or other sources of pressure.

10. “Backflow preventer” means a device or method to prevent backflow into the potable
water system.

11. “Backflow prevention assembly general tester” means those individuals holding a
testing certificate from a nationally recognized backflow certification organization approved by
the State Health Officer. Such individuals are not required to be a licensed plumber and are
authorized to perform tests of backflow prevention devices and methods. When such devices or
methods are located on private property, a backflow prevention assembly general tester is not
authorized to install, repair, or maintain such devices or methods. A general tester may perform
installation, maintenance or repairs, if the backflow prevention device is on public property, after
having obtained approval from the water purveyor.
12. “Backflow prevention assembly technician” means a water supply protection
specialist licensed by the State Plumbing Board of Louisiana pursuant to LA. R.S. 37:1361, et
seq., and its implementing regulations (LAC 46:LV.101, et seq.). All water supply protection
specialists are Louisiana licensed plumbers who hold such a special endorsement on their
plumbing license. Such individuals are authorized to test, install, repair, and maintain backflow
prevention devices and methods.

13. “Back-siphonage” means the flowing back of used, contaminated, or polluted water
from a plumbing fixture or vessel into a water supply pipe due to a negative pressure in such
pipe. (See “backflow”)

14. “Code” The word “code” or “this code”, when used alone, shall mean these regulations,
subsequent amendments thereto or any emergency rule or regulation which the administrative
authority having jurisdiction may lawfully adopt.

15. “Containment” means a method of backflow prevention, which requires the installation
of an air gap or a backflow prevention assembly immediately following the water meter, or as
close to that location as deemed practical by the administrative authority.

16. “Contamination” means an impairment of the quality of the potable water, which
creates an actual hazard to the public health through poisoning or through the spread of disease
by sewage, industrial fluids or waste. Also defined as “high hazard.”

17. “Cross-connection” means any connection or arrangement, physical or otherwise,
between a potable water supply system and any plumbing fixture or any tank, receptacle,
equipment or device, through which it may be possible for non-potable, used, unclean, polluted
or contaminated water, or other substances, to enter into any part of such potable water system
under any condition.

18. “Customer” means the owner, operator, or occupant of a building or property, which
has a water service from a public water system, or the owner or operator of a private water
system, which has a water service from a public water system. “Customer” shall not include any
residential connection used for dwelling purposes, unless: i.) the residence is also used as a
business premises and the home-based business or occupation involves operation of a home-
based business or occupation which the water purveyor or City Inspector deems a potentially
significant and high hazard to the City water supply; ii.) the domestic water service provided is
also used for a landscape irrigation system; or, iii.) a separate water service has been installed
for landscape irrigation and other non-domestic purposes.

19. “Degree of hazard” means the rating of a cross-connection or water service, which
indicates if it has the potential to cause contamination or pollution.

20. “Domestic sewage” means the liquid and water-borne wastes derived from the ordinary
living processes, free from industrial wastes, and of such character as to permit satisfactory
disposal, without special treatment, into the public sewer or by means of a private sewage
disposal system.

21. “Double check valve backflow prevention assembly” means a backflow prevention
device consisting of two independently acting internally loaded check valves, four properly
located test cocks, and two isolation valves.

22. “Existing work” means a plumbing system, or any part thereof, which has been
installed prior to the effective date of this Code.

23. “Fire protection system” means any system used for fire protection or suppression with
a direct connection to the public water supply, including but not limited to sprinklers, stand-
pipes, and siamese connections.

24. “High hazard” see contamination.

25. “High hazard cross connection” means a cross-connection which may cause an
impairment of the quality of the potable water by creating an actual hazard to the public health,
through poisoning or through the spread of disease by sewage, industrial fluids, or waste.

26. “Industrial waste” means any and all liquid or water-borne waste from industrial or
commercial processes, except domestic sewage.

27. “Isolation” means a method of backflow prevention in which a backflow prevention
assembly is located at the cross-connection rather than at the water service entrance.

28. “Labeled” means equipment or materials bearing a label or listing agency.

29. “Liquid water” means the discharge from any fixture, appliance or appurtenance in
connection with a plumbing system, which does not receive fecal matter.

30. “Listed” means equipment or materials included in a list published by a listing agency
that maintains periodic inspection or current production of listed equipment or materials and
whose listing states either that the equipment or material complies with approved standards or
has been tested and found suitable for use in a specified manner.

31. “Listing agency” means an agency accepted by the administrative authority which is in
the business of listing or labeling and which maintains a periodic inspection program on current
production of listed models, and which makes available a published report of such listing in
which specific information is included that the product has been tested to approved standards and
found safe for use in a specific manner. (e.g., USC-FCCCHR, ASSE, etc.)

32. “Low hazard” see pollution.
33. “Low hazard cross-connection” means a cross-connection, which may cause an
impairment of the quality of potable water to a degree which does not create a hazard to the
public health, but which does adversely and unreasonably affect the aesthetic qualities of such
potable waters for domestic use.

34. “Main” means the principal artery of any system of continuous piping to which
branches may be connected.

35. “May” is a permissive term.

36. “Pharmaceutical-grade antifreeze” means a food-grade antifreeze such as an inhibited
propylene glyco-based fluid.

37. “Point of entry” means the point of connection to the potable water system.

38. “Point of introduction” means the point at which any additive is introduced to the
water supply system.

39. “Pollution” means an impairment of the quality of the potable water to a degree which
does not create a hazard to the public health but which does adversely and unreasonably affect
the aesthetic qualities of such potable waters for domestic use. Also defined as “low hazard.”

40. “Potable water” means water, which is satisfactory for drinking, culinary, and domestic
purposes and meets the requirements of the state and city departments of health.

41. “Reduced pressure principle backflow prevention assembly” means a backflow
prevention device consisting of two independently acting internally loaded check valves, a
differential pressure relief valve, four properly located test cocks, and two isolation valves.

42. “Sewage” means any liquid waste containing animal or vegetable matter in suspension
or solution and may include liquids containing chemicals in solution.

43. “Shall” The word “shall” is a mandatory term.

44. “Table D 104" refers to the table marked D 104 in appendix D of the Louisiana State
Plumbing Code, 2000 Edition. (Known as the containment device table)

45. “Table D 105" refers to the table marked D 105 in appendix D of the Louisiana State
Plumbing Code, 2000 Edition. (Known as the fixture isolation table)

46. “Section D 106" refers to the Section marked D 106 in appendix D of the Louisiana
State Plumbing Code, 2000 Edition.

47. “Water service” Depending on the context, “water service” means the physical
connection between a public water system and a customer's building, property, or private water
system, or the act of providing potable water to a customer.

48. “Water supply system” means the water supply system of a building or premises
consisting of the building supply pipe, the water distributing pipes and the necessary connecting
pipes, fittings, control valves, and all appurtenances carrying or supplying potable water in or
adjacent to the building or premises.

49. “Water Purveyor” means the Henderson-Nina Water System.

Sec. 13-6. Administrative Authority.

(a) The Water Purveyor shall have the right to enter, with the consent of the
 customer, or upon the basis of a suitable warrant issued by a court of
 appropriate jurisdiction, any property to inspect for cross-connections.

(b) The State of Louisiana will approve training programs for “backflow
 prevention assembly technicians” and register “backflow prevention
 assembly technicians” who successfully complete a training program
 approved by the State Plumbing Board of Louisiana as per LA. R.S.
 37:1367(G) and LAC 46:LV.310, all of which applies to licensed plumbers.

 In addition, the State Health Officer, through the LSPC, 2000 Edition, does
 accept certain persons as “general testers” per Section D108.1.1 thereof.
 Such individuals are known and defined herein as “backflow prevention
 assembly general testers”. The limitations of jurisdiction/authority of
 “backflow prevention assembly general testers” are described within said
 definition.

(c) The Administrative Authority shall collect a fee of $25.00 for each
 inspection done by the Water Purveyor. The inspection will only be for the
 water purveyor to make sure that the air gap or backflow prevention device
 is in place and is the proper cross-connection control device or method used
 in accord with Table D104 and Section D106.

(d) The Administrative Authority and the Water Purveyor shall maintain records
 of cross-connection hazard surveys, and the installation, testing, and repair
 of all backflow prevention assemblies installed for containment purposes.

(e) Notwithstanding anything herein to the contrary, the Administrative
 Authority and Water Purveyor are authorized to take additional actions
 which may not be specifically covered herein that are deemed necessary to
 protect the community water supply from potential or actual cross connections
 in accord with the requirements of the Louisiana State Plumbing Code, 2000
 Edition.

 Sec. 13-7. Water Services.

1. A. New water services.

 1. Plans shall be submitted to the Water Purveyor for review on all new water
 services in order to determine the degree of hazard.

 2. The water purveyor shall approve the type of backflow prevention assembly or
 method required for containment based on the requirement of Table D104 and degree of
 hazard. If a cross-connection is not listed in Table D104, the Water Purveyor shall use
 Table B1 of the “Manual for the Selection, Installation, Maintenance, and Field Testing of
 Backflow Prevention Devices” (CAN/CSA Standard B64.10-1994) as a guide to
 determine the type of device to require. (This document is referred to in Table 606 of the
 LSPC, 2000 Edition.)

 1. The Water Purveyor shall require the installation of the appropriate backflow
 prevention assembly or method for containment before the initiation of water service.

2. A. Existing water service.

 1. Any changes of, or additions to, existing water services shall be treated as new
 water services for the purpose of this ordinance.

 2. Within six (6) months after adoption of this ordinance, the administrative
 authority shall publish and make available to each customer a copy of the standards used
 to determine the degree of hazard.

 3. Each customer shall survey the activities and processes, which receive water
 service and shall report to the Water Purveyor if cross-connections exist and the degree of
 hazard. Upon a finding of hazard, the customer shall cause the appropriate backflow
 prevention assembly or method to be installed in a timely fashion.

 4. For existing water services, the Water Purveyor may inspect the premises to
 determine the degree of hazard. When high hazard cross-connections are found the Water
 Purveyor shall:

 1. I. Develop a schedule of compliance which the customer shall follow, or
 2. ii.Terminate the water service until a backflow prevention assembly or
 method for containment required by the Water Purveyor has been
 installed.

 5. Failure of the Water Purveyor to notify a customer that the customer has a high
 hazard cross-connection and should install backflow prevention assemblies or methods
 for containment in no way relieves the customer of the responsibility to comply with all
 requirements of this section.

Sec. 13-8. Customer Duties.

(a) The customer shall be responsible for ensuring that no cross-connections
 exist without approved backflow protection within the customer's premises
 starting at the point of service from the public potable water system.

(b) The customer shall, at the customer's own expense, cause installation,
 operation, testing and maintenance of the backflow prevention assemblies
 required by the administrative authority. The customer shall advise the
 water purveyor in advance of when a device is to be tested to allow the water
 purveyor the opportunity to witness the test.

(c) Within fifteen (15) days after testing and/or repairs are completed, the
 customer shall provide the administrative authority with copies of records of
 the installation and of all tests and repairs made to the backflow prevention
 assembly on a form provided by the administrative authority.

(d) In the event of a backflow incident, the customer shall immediately notify
 the Water Purveyor of the incident and take steps to confine the
 contamination or pollution. Water service will not be restored until
 corrective action is taken and approved after inspection by the Water
 Purveyor.

(e) In accordance with Section D108.3.4 of the LSPC, 2000 Edition, the
 customer shall maintain records of installations, tests, repairs, overhauls, or
 replacements of backflow prevention devices or methods for at least 5 years
 and, upon request, such records shall be made available to the administrative
 authority.
 Sec. 13-9. Requirements.

3. A. Water Purveyor requirements:

 1. For premises existing prior to the start of this program, the Water Purveyor will
 perform evaluations and inspections of plans and/or premises and inform the customer by
 letter of any corrective action deemed necessary, the method of achieving the correction,
 and the time allowed for the correction to be made. Ordinarily, ninety (90) days will be
 allowed, however, this time period may be shortened depending upon the degree of
 hazard involved and the history of the device(s) in question.

 2. The Water Purveyor will not allow any cross-connection to remain unless it is
 protected by an approved backflow preventer or an air gap for which a permit has been
 issued and which will be regularly tested to insure satisfactory operation.

 3. The Water Purveyor shall notify the Customer by letter of any failure to comply
 at the time of the first re-inspection or immediately following the first re-inspection. The
 Water Purveyor will allow an additional fifteen (15) days for the correction. In the event
 the Customer fails to comply with the necessary correction by the time of the second re-
 inspection, the Water Purveyor will notify the Customer by letter that the water service to
 the Customer’s premises will be terminated within five (5) days from the customer’s
 receipt of such letter. In the event that the Customer informs the Water Purveyor of
 extenuating circumstances as to why the correction has not been made, a time extension
 may be granted by the Water Purveyor but in no case will exceed an additional thirty (30)
 days.

 4. Notwithstanding anything to the contrary, if the Water Purveyor determines at
 any time that a serious threat to the public health exists, the water service will be
 terminated immediately.

 5. The Water Purveyor shall have on file a list of Private Contractors who are
 certified backflow device testers and/or repairers. All charges for these tests, repairs, etc.,
 will be paid by the Customer of the building or property.

 6. The Water Purveyor will begin initial premise inspections to determine the nature
 of existing or potential hazards, following the approval of this program by the city
 Council and Mayor, during the calendar year (2005). Initial focus will be on high hazard
 industries and commercial premises.

4. B. Customer requirements:

 1. The Customer shall be responsible for the elimination or protection of all cross-
 connections on his premises.
2. The Customer, after having been informed by a letter from the Water Purveyor,
shall at his expense, install, maintain, and test or have tested, any and all backflow
prevention devices or methods on his premises.

3. The Customer shall correct any malfunction of the backflow prevention device
or method which is revealed by periodic testing.

4. The Customer shall inform the Water Purveyor of any proposed or modified
cross-connection and also any existing cross-connection of which the Customer is aware
but has not been found by the Water Purveyor.

5. The Customer shall not install a bypass around any backflow prevention device
or method unless there is a backflow prevention device or method of the same type on the
bypass. Customers who cannot shut down operation for testing of the device(s) or
method(s) must supply additional devices or methods necessary to allow testing to take
place.

6. The Customer shall install backflow prevention devices or methods in a manner
approved by the Water Purveyor and in conformance with the installation requirements of
Section 606 of the LSPC, 2000 Edition. In addition, devices having an atmospheric port
or discharge shall be installed such that the port or discharge point is located at least 24
inches above the highest flood level which may have occurred in the previous 10 year
period.

7. The Customer shall install only backflow prevention devices or methods
approved by the Water Purveyor.

8. Any Customer having a private well, auxiliary water supply or other private
water source, must have a permit if the well, auxiliary water supply or source is cross-
connected to the Water Purveyor's system. Permission to cross-connect may be denied by
the Water Purveyor. The customer may be required to install a backflow prevention
device or method at the service entrance if a private water source is maintained, even if it
is not cross-connected to the Water Purveyor's system.

9. In the event the Customer installs plumbing to provide potable water for
 domestic purposes, which is on the Water Purveyor's side of the backflow
 prevention device or method, such plumbing must have its own backflow
 preventer installed.

10. The Customer shall be responsible for the payment of all fees for permits, annual
or semi-annual device or method testing, re-testing in the case that the device or method
fails to operate correctly, and second re-inspections for non-compliance with the Water
Purveyor's requirements.
Sec. 13-10. Required backflow prevention assemblies or methods for
containment.

A. Water Service Assemblies:

 An air gap or an approved reduced pressure principle backflow prevention
 assembly is required for water services having one or more potential cross-
 connections which the administrative authority classifies as high hazard as
 defined by tables D104 and D105.

B. Fire Protection System Assemblies:

 1. All proposed installations of fire suppression systems shall be reviewed by the
 Henderson-Nina Water System Department of Inspections to determine the appropriate type
 of backflow prevention devices or methods required.

 2. For all proposed fire suppression systems using antifreeze, a reduced pressure
 principle (#10 on Table D104) backflow prevention device shall be installed at the point
 of entry. The customer shall provide the City with the design and chemical usage of the
 fire suppression system.

 3. All existing fire suppression systems shall meet the requirements of Sec. 13-9
 above. An inspection by a fire suppression specialist shall be done to determine whether
 antifreeze has been utilized in the suppression system. The inspection shall be done at
 the expense of the customer. If it cannot be certified that antifreeze has been used, then a
 backflow prevention device shall be installed as prescribed by Table D104 and as
 approved by the Henderson-Nina Water System Department of Inspections. Installation
 shall be at the expense of the customer. The required backflow prevention devices or
 methods shall be installed at the time the system is repaired or changed, or within twelve
 (12) months after adoption of this ordinance, whichever occurs first.

 4. In the event cross-connections, such as those found in using auxiliary water
 supply systems or in providing other water additives such as foaming agents, are
 necessary for the proper operation of the fire suppression system, then an air gap or a
 reduced pressure principle backflow prevention device shall be installed in an approved
 manner.

Sec. 13-11. Registration.

A. Technician Registration:
 Any backflow prevention assembly technician licensed by the State of
Louisiana must register with the administrative authority before performing work
within the Henderson-Nina Water System service area . Any licensed backflow prevention
assembly technician shall include his or her state registration number on all
correspondence and forms required by or associated with this ordinance.

B. General Tester Registration:

 Any backflow prevention assembly general tester shall present a copy of
his/her testing certificate from a nationally recognized backflow certification
organization and shall register with the administrative authority before performing
work within the Henderson-Nina Water System service area.

Sec. 13-12. Non-compliance by registered technicians or general testers.

(a) The local registration of a technician or general tester may be revoked or
 suspended for a period of up to two (2) years for non-compliance with this
 ordinance.

(b) Any of the following conditions constitute non-compliance:

 1. Improper testing or repair of backflow prevention assemblies or methods;

 2. Improper reporting of the results of testing or of repairs made to backflow
 prevention assemblies or methods;

 3. Failure to meet registration requirements;

 4. Related unethical practices.

Sec. 13-13. Installation of backflow prevention assemblies or methods.

(a) The required backflow prevention assemblies or methods for containment
 shall be installed in the manner recommended by the manufacturer and in
 accord with the requirements of Section 606 of the LSPC, 2000 Edition,
 immediately following the meter or as close to that location as deemed
 practical by the administrative authority. In any case, it shall be located
 upstream from any branch piping. Installation at this point does not
 eliminate the responsibility of the customer to protect the water supply
 system from contamination or pollution between the backflow prevention
 assembly or methods and the water main.

(b) Reduced pressure principle backflow prevention assemblies shall be
 installed so as to be protected from flooding. The port or discharge point
 shall be installed such that it is located at least 24 inches above the highest
 flood level, which may have occurred in the previous 10-year period.

(c) Reduced pressure principle backflow prevention assemblies or methods shall
 not be installed in underground vaults or pits, unless a gravity drainage
 system (designed by a Louisiana registered engineer) for the particular site
 has been approved by the state health officer. (The intent of the exception to
 this section is to possibly allow below grade installations on particular sites
 or lots having sufficiently hilly ground at the proposed location of the device
 such that when the vault or pit is constructed it may be equipped with
 positive gravity drainage openings as to prevent any part of the device from
 being submerged. A recommended design standard for such an installation
 may be found in Sections 606.4.1 and 606.4.2 of the 1994 Standard
 Plumbing Code.)

(d) All backflow prevention assemblies or methods shall be protected from
 freezing. Those devices used for seasonal services may be removed in lieu
 of being protected from freezing; however, the devices must be reinstalled
 and tested by a registered backflow prevention assembly technician prior to
 service being reactivated.

(e) If hot water is used within the water supply system, thermal expansion shall
 be provided for when installing a backflow prevention assembly or method
 for containment in accordance with Section 613.2 of the LSPC, 2000
 Edition.

(f) Provisions shall be made to convey the discharge of water from reduced
 pressure principle backflow prevention assemblies or methods to a suitable
 drain through an air gap.

(g) No backflow prevention assemblies or methods shall be installed in a place
 where they would create a safety hazard, such as, but not limited to, over an
 electrical panel, or above ceiling level.
(h) If interruption of water service during testing and repair of backflow
 prevention assemblies or methods for containment is unacceptable to the
 customer, another backflow prevention assembly or method of equivalent or
 higher protection, sized to handle the temporary water flow needed during
 the time of testing or repair, shall be installed in parallel piping.

(i) All backflow prevention assemblies or methods shall be installed so that
 they are accessible for testing.

(j) All shut-off valves shall conform to the current edition of the 2000 Edition
 Louisiana State Plumbing Code requirements for either ball or resilient seat
 gate valves. Full port ball valves shall be used on assemblies installed in
 piping two inches or smaller, and full port resilient wedge-type shut off
 valves on assemblies installed in piping larger than two inches.

Sec. 13-14. Testing of backflow prevention assemblies or methods.

(a) Testing of backflow prevention assemblies or methods shall be performed by
 a backflow prevention assembly technician or by a backflow prevention
 assembly general tester registered with the administrative authority. The
 costs of tests required in the following paragraphs shall be borne by the
 customer.

(b) Backflow prevention assemblies or methods shall be tested upon
 installation; when cleaned, repaired, or overhauled; when relocated and,
 shall be tested and inspected at least once annually. Backflow prevention
 devices shall be tested in accordance with CAN/CSA Standard B64.10-1994
 or ASSE Standard 5010-1998.

(c) Backflow prevention assemblies or methods which are in place, but have
 been out of operation for more than three (3) months, shall be tested before
 being put back into operation. Backflow prevention assemblies or methods
 used in seasonal applications shall be tested before being put into operation
 each season.

(d) Any backflow prevention assembly or method which fails a periodic test
 shall be repaired or replaced by a backflow prevention assembly technician
 when such assembly is located on private property. When such a device is
 located on public property, a backflow prevention assembly general tester
 may repair or replace the device if authorized by the water purveyor. When
 water service has been terminated for non-compliance, the backflow
 prevention assembly or method shall be repaired or replaced prior to the
 resumption of water service. Backflow prevention assemblies or methods
 shall be re-tested by a registered backflow prevention assembly technician or
 by a backflow prevention assembly general tester immediately after repair or
 replacement.

(e) The Henderson-Nina Water System Department of Inspections may require
 backflow prevention assemblies or methods to be tested at any time in
 addition to the annual testing requirement.

(f) The registered backflow prevention assembly technician or backflow
 prevention assembly general tester shall report the testing of backflow
 prevention assembly or method to the customer and to the administrative
 authority within fifteen (15) days of the test.

(g) The administrative authority may require, at its own cost, additional tests of
 individual backflow prevention assemblies or methods as it shall deem
 necessary to verify test procedures and results.

Sec. 13-15. Repair of backflow prevention assemblies or methods.

(a) All repairs to backflow prevention assemblies or methods on private
 property shall be performed by a licensed plumber holding a special “water
 supply protection specialist” endorsement on his plumbing license, herein
 defined as “backflow prevention assembly technician”.

(b) After obtaining approval from the water purveyor, a “backflow prevention
 assembly general tester” may perform repairs to backflow prevention
 assemblies or methods located on public property.

(c) The registered backflow prevention assembly technician or backflow
 prevention assembly general tester shall not change the design, material, or
 operational characteristics of a backflow prevention assembly or method
 during repair or maintenance, and shall use only original manufacturer
 replacement parts, if available; if not available, shall use replacement parts
 approved by the Department of Inspections.

(d) The registered backflow prevention assembly technician or backflow
 prevention assembly general tester shall report the repair, overhaul, or
 replacement of any backflow prevention assembly or method to the
 customer and to the Henderson-Nina Water System Department of Inspections on
 the form provided by the Henderson-Nina Water System Department of Inspections
 within fifteen (15) days of the repair.

Sec. 13-16. Customer non-compliance.

(a) The water service may be discontinued in the case of non-compliance with
 this policy. Non-compliance includes, but is not limited to, the following:

 1. Refusal to allow the administrative authority or water purveyor access to the
 property to inspect for cross-connection;

 2. Removal of a backflow prevention assembly or method, which has been required
 by the administrative authority.

 3. Bypassing of a backflow prevention assembly or method, which has been
 required by the administrative authority.

 4. Providing inadequate backflow prevention when potential or actual cross-
 connections exist.

 5. Failure to install a backflow prevention assembly or method, which has been
 required by the administrative authority.

 6. Failure to test and/or properly repair a backflow prevention assembly or method
 as required by the administrative authority.
 7. Failure to comply with the requirements of this ordinance.

Sec. 13-17. Penalty for violation.

 Apart from any other penalties or sanctions imposed by local or state
laws, any person found guilty of violating any provision of this Section shall
be guilty of a misdemeanor and, upon conviction thereof, shall be punished
in accordance with City Code. Each day that a violation is allowed to
continue shall constitute a separate and distinct violation.

The Henderson-Nina Water System Board of Directors adopted this policy
on March 16, 2009.